Anotace:
The direct contact of a tree or a branch of tree with Covered Conductors (CC) overhead lines causes Partial Discharges (PD) inside the insulation. The presence of PD degrades the insulation systems and eventually destroys insulation, which may lead to power delivery interruption. The detection and diagnosis of PD is an important tool to address the problem of tree caused faults in forested terrains. The PD occurs in the impulse component of the signal, which is usually measured by Rogowski coil (current signal) or single layer inductors (voltage signal). In this paper, we introduce a possibility to detect the tree caused faults with the usage of whip antenna. The advantage of the antenna is a very low price and the possibility to install antenna under voltage. The disadvantages are sensitivity to ferromagnetic materials and impossibility to distinguish affected phase. The measurements were carried out in the real environment in forested terrain in Jeseniky Mountains. The real environment is different from a laboratory conditions due to heavy noise (e.g. corona, radio emissions). This paper provides an examination of the background noise from the antenna signal. The experimental results indicate that the antenna may be successfully used instead of the current approach.